Approvals/certifications |
Certified to EN54-2/4 by the LPCB (0832-CPD-0758). |
Protocol/compatibility |
Syncoln/Apollo XP95/Discovery. |
Mains supply |
230V 50/60Hz. |
Mains rated current |
1.35A maximum. |
Internal power supply |
27Vdc nominal. |
Total output current limited to |
5A @ 230Vac (Imax.A 4A; Imin. 12mA). |
Battery charge capacity |
7Ah min to 18Ah max. |
Quiescent current |
Varies depending on the panel’s configuration – refer to our ZFP loop/battery calculation tool for details. |
Max battery size and type |
2 x 12V 18Ah VRLA connected in series. |
No. of loop drivers |
1, 2 or 4 (dependent on model purchased). |
Max. loop output current |
500mA (25V min; 34V max). |
Max. loop length |
1KM. |
Max. addressable devices per loop |
126. |
No. of conventional sounder circuits |
2 (Max. length per circuit is 500m). |
EOL resistor value |
6800Ω 5% Tol. 0/25W (blue, grey, red, gold). |
Max. sounder output current |
2 x 1A. |
Auxiliary relays |
2 x Programmable Relays (programmable from C&Es). 1 x Fault Relay (active when no faults are present). Volt free single pole changeover. Max. switch current 1A; Max. switch voltage 30Vdc. |
Other outputs |
24V Aux. Power (19.5V min, 28V max). Protected by a resettable fuse. Max. current 100mA. |
Auxiliary inputs |
2 x Programmable Inputs (programmable from C&Es). Connect to 0V to trigger, Max. input voltage 27V (non-latching). |
PC connection |
Via a galvanically isolated USB socket on the Z41 control module. |
Pager/DECT connection |
RS232. ESPA compatible. |
Graphics interface/diagnostics connection |
RS485. Drax compatible. |
Network connection |
RS485 hi-integrity multi-path fault tolerant network connection via optional ZHN network card. Max 128 network nodes (up to 64 main panels & 64 compact controllers). |
Indicators |
Full-colour 480 x 272 pixel touchscreen, all relevant EN54 indicators plus 5 programmable indicators. Additional indicators dependent on Switch & Indicator module fitted. |
Controls |
Interactive touchscreen with menu sensitive buttons; 1 x keyswitch allowing direct access to Access Level 2. Additional controls dependent on Switch & Indicator module fitted. |
Connections |
Fixed, largest acceptable conductor size 1mm2. |
Expansion connections |
RS485 peripheral bus connection allows the connection of up to 15 ‘A-Bus’ PCBs (2 control cores plus screen plus 2 cores for power). |
Product dimensions (mm) |
450 W x 462 H x 127 D. |
Construction & finish |
Light grey textured mild steel, 1.2mm Zintec. RAL7035 epoxy paint. |
IP Rating |
IP30. |
Weight |
TBC. |
Operating conditions/temperature |
-5ºC to +40ºC. Max relative humidity: 95%. |
1 Loop Variants |
Z0130000S/X (Blank Module); Z013020NS/X (20 Zonal LEDs); Z013040NS/X (40 Zonal LEDs); Z013020PS/X (20 Zonal LEDs, Printer, 2 Keyswitches). |
2 Loop Variants |
Z0230000S/X (Blank Module); Z023020NS/X (20 Zonal LEDs); Z023040NS/X (40 Zonal LEDs); Z023020PS/X (20 Zonal LEDs, Printer, 2 Keyswitches). |
4 Loop Variants |
Z0430000S/X (Blank Module); Z043020NS/X (20 Zonal LEDs); Z043040NS/X (40 Zonal LEDs); Z043020PS/X (20 Zonal LEDs, Printer, 2 Keyswitches). |
6 Loop Variants |
N/A. |
8 Loop Variants |
N/A. |